50 sats \ 1 reply \ @WeAreAllSatoshi 9h \ on: Home mining heating setup advice? bitcoin_Mining
Zapped for visibility. This could be interesting to read
Thanks for the boost. I thought there’d be more folks chiming in on here. Anyway, here’s a response I got from the Heatpunks telegram group.
As for the wires, typically you size a circuit based of the 80% rule. So 1 jpro takes 3200 watts. That's 13.3 amps at 240v. 13.3 / 20 is less than 80% so you're safe to have 1 machine on 1 20 amp circuit. Which is 12 gauge romex wire. Scale this accordingly.
Usually we also put the l6-30r plugs at the end of the circuit since that's the outlet PDUS take. Some people direct wire the machines to the panels. As for breakers. Get whatever is currently in your panel so they match. They have all this at depot (assuming American)